3-Phase & Single-Phase Transformer kVA Rating Calculator
Calculate full-load secondary current (FLA), primary current, and recommended standard transformer kVA size for commercial and industrial electrical distribution.
Parameters & Inversions
Deterministic EngineCalculated Output Metrics
Analytical Proof & Invariants
Machine Precision3-Phase kVA = (√3 × Volts_LL × Amps) / 1000 | FLA = (kVA × 1000) / (√3 × Volts_LL)
Step-by-Step Mathematical Derivation
For 3-phase: S = √3 × V × I / 1000. S_base = 1.732 × 208V × 180A / 1000 = 64.84 kVA.
S_design = S_base × (1 + Margin% / 100). With 25% spare margin: 64.84 × 1.25 = 81.05 kVA.
Standard 3-phase dry-type transformer ratings are 15, 30, 45, 75, 112.5, 150, 225, 300, 500 kVA. Sizing above 81.05 kVA yields a 112.5 kVA unit.
I_primary = (kVA × 1000) / (√3 × V_primary). For 112.5 kVA at 480V: 112,500 / (1.732 × 480) = 135.3A.