3-Phase Power Factor Correction & Capacitor Sizing Calculator
Calculate required capacitor kVAR bank size to correct lagging electrical power factor from inductive motors, eliminating utility penalty surcharges.
Parameters & Inversions
Deterministic EngineCalculated Output Metrics
Analytical Proof & Invariants
Machine PrecisionRequired kVAR = P × (tan(θ₁) - tan(θ₂)) | θ = arccos(PF)
Step-by-Step Mathematical Derivation
θ₁ = arccos(0.76) = 40.54°. tan(40.54°) = 0.855. θ₂ = arccos(0.95) = 18.19°. tan(18.19°) = 0.329.
Q_cap = P_kw × (tan(θ₁) - tan(θ₂)). For 250 kW: 250 × (0.8553 - 0.3287) = 131.65 kVAR.
S₁ = 250 / 0.76 = 328.9 kVA. S₂ = 250 / 0.95 = 263.2 kVA. Freed electrical transformer capacity = 65.7 kVA.
I = S / (√3 × V_ll). Original Current = 328,900 / (1.732 × 480) = 395.6A. Corrected Current = 263,200 / (1.732 × 480) = 316.5A (79.1A reduction).