Heating & Cooling Degree Days (HDD / CDD) Thermal Audit Calculator
Calculate weather-normalized annual building thermal load in therms and kWh using Heating Degree Days (HDD) and Cooling Degree Days (CDD).
Parameters & Inversions
Deterministic EngineCalculated Output Metrics
Analytical Proof & Invariants
Machine PrecisionHDD = Σ max(0, 65°F - T_mean) | Annual Heat BTU = UA_building × HDD × 24
Step-by-Step Mathematical Derivation
Building UA represents heat loss per degree Fahrenheit temperature difference. For a 2,400 sq ft home: Standard envelope UA ≈ 0.125 BTU/hr·sqft·°F × 2,400 = 300 BTU/hr·°F.
Q_heat = UA × HDD × 24 hrs/day. 300 × 4,200 × 24 = 30,240,000 BTU/year.
1 Therm = 100,000 BTU. Assuming 85% AFUE furnace: Fuel Therms = (30,240,000 / 0.85) / 100,000 = 355.8 Therms.
Cooling BTU = UA × CDD × 24 = 300 × 1,400 × 24 = 10,080,000 BTU. With 15 SEER AC: 10,080,000 / (15 × 1000) = 672 kWh.