Voltage Drop & Wire Gauge (AWG) Calculator
Calculate electrical voltage drop, percentage loss, and proper American Wire Gauge (AWG) conductor sizing for single-phase copper circuits.
Parameters & Inversions
Deterministic EngineCalculated Output Metrics
Analytical Proof & Invariants
Machine PrecisionVoltage Drop (VD) = [2 × K × I × Length (ft)] / Circular Mils (CM)
Step-by-Step Mathematical Derivation
Voltage Drop V_d = 2 × K × I × L / CM, where K = 12.9 ohms-cmil/ft for copper at 75°C, I is current in amps, L is one-way distance in feet, and CM is circular mils.
14 AWG = 4,110 CM; 12 AWG = 6,530 CM; 10 AWG = 10,380 CM; 8 AWG = 16,510 CM; 6 AWG = 26,240 CM; 4 AWG = 41,740 CM.
National Electrical Code (NEC) Section 210.19(A) recommends that voltage drop not exceed 3% on branch circuits and 5% total across feeder and branch combined.